Enter a liquid's flash point (and initial boiling point) to get its CLP flammable liquid category, hazard statement, signal word and pictogram.
| Category | Criteria | H | Signal word |
|---|---|---|---|
| Flam. Liq. 1 | Flash point < 23 °C and initial boiling point ≤ 35 °C | H224 | Danger |
| Flam. Liq. 2 | Flash point < 23 °C and initial boiling point > 35 °C | H225 | Danger |
| Flam. Liq. 3 | Flash point ≥ 23 °C and ≤ 60 °C | H226 | Warning |
Above 60 °C: not classified as a flammable liquid. All three categories carry the GHS02 flame pictogram.
Based on CLP Annex I section 2.6. A mixture's flash point should be measured, or reliably calculated, for the mixture itself.